Anhui Kesidi Electric Co.,Ltd
ZW32-24KV Outdoor high voltage automatic recloser
ZW32-24KV Outdoor high voltage automatic recloser

1.Overview

1.1 Main purpose and scope of application

The ZW32-24 outdoor AC high-voltage vacuum circuit breaker (hereinafter referred to as the "circuit breaker")is a new generation of outdoor vacuum circuit breakers developed by introducing advanced foreign technology and combining the characteristics of China's power industry. 

This circuit breaker is designed for three-phase AC 50/60HZ and has a rated voltage of 24KV, making it suitable for outdoor high-voltage switchgear. It is primarily used in the distribution systems of urban and rural power grids, substations, as well as industrial and mining enterprises, for opening and closing load currents, overload currents, and short-circuit currents. Due to the special properties of vacuum circuit breakers, they are particularly suitable for applications requiring frequent operations and oil-free retrofits. 

 This model of circuit breaker adopts a three-phase separated pole structure, ensuring that a fault in one phase will not cause a three-phase short circuit. The vacuum arc extinguishing chamber is housed within the insulating sleeve of each phase, eliminating the risk of short-circuit faults caused by condensation. The external insulation employs imported outdoor epoxy resin or silicone rubber materials, providing excellent hydrophobic and anti-fouling properties, making it suitable for outdoor environments with high weather resistance requirements and harsh operating conditions. The overall structure of the circuit breaker is compact, with a small footprint,light weight, and easy installation. The interior of the cabinet is filled with transformer oil but contains no sulfur hexafluoride gas, meeting the requirements for oil-free retrofits and environmental protection. 

2. Product standards

The standards that the circuit breaker meets GB1984: High-voltage Circuit Breaker GB/T11022: Common Technical Requirements for High-voltage Switchgear and Control Equipment JB3855: 3. 6~40. 5kV Outdoor AC High-voltage Vacuum Circuit Breaker DL/T403: 12~40. 5KV AC High-voltage Vacuum Circuit Breaker Ordering Technical Conditions IEC56: AC high-voltage Circuit Breaker

3.Environmental conditions for use

a. Environmental temperature: maximum temperature - 40℃, minimum temperature - 45℃, maximum daily temperature difference - 25℃;
b. Environmental humidity: Daily average relative humidity≤95%, monthly average relative humidity≤90%,daily average saturated vapor pressure≤2. 2×10-3MPa, monthly average saturated vapor pressure ≤1. 8×10-3MPa;
c. Altitude: not exceeding 1000m; 
d. The seismic intensity shall not exceed level 8;
e. Wind speed: not exceeding 35m/s;
f. Pollution level: IV;
g. Places without fire, explosion, chemical corrosion, and frequent severe vibration. 
   When the usage conditions exceed the above range, the allowable range and technical measures should be determined through consultation with the supplier. 

4. Rated Parameters

Table 1 : Main Rated Parameters

No . Name Unit Parameters
1      Rated voltage KV 24
2      Rated frequency HZ 50 
3 
Rated
insulation
level
1-minute rated power
frequency withstand voltage
KV
Wet: 50
Dry: 60 (phase to phase ,relative to
the ground)/65 (fracture surface)
Rated lightning
impulse withstand
voltage (peak value)
Alternating and
facing the ground
95 
Fracture Surface 125 
4  Rated current A 630 、1250
5  Rated short circuit breaking current KA 20 、25
6  Rated short-circuit closing current (peak) 50 、63
7  Rated dynamic stability current (peak value) 50 、63
8  Rated thermal stability current (effective value) 20 、25
9  Rated short-circuit breaking current times Times 30 
10  Rated thermal stability time S 4 
11  Rated operating sequence   CO-0 .3S-CO-180s-CO
12  Mechanical life Times 10000 
13  Allowable wear thickness of contacts mm 3 
14  Secondary circuit 1-minute power frequency withstand voltage KV 2 
15  Weight kg 120/160


Table 2: Main Rated Parameters

No . Name Unit Parameters
1     Clearance between open contacts mm 12±1
2     Contact over-travel 3.5±0.5
3     Interphase center distance 380±1 .5
4     Bouncing time of closing contact ms ≤2
5     Three-phase on-off asynchrony ≤2
6     Opening time 18~45
7     Closing time (electric closing) 25~60
8     Average opening speed m/s 1.1~1.7
9     Average closing speed 0.5~1.0
10     Resistance of each phase conductive circuit μΩ ≤80  (Band G≤150)

 

5.Outline dimension diagram